Applied Motor Controls
Duplex Booster Pump Control Panels

Product Description
Duplex Pump Controls Panels are designed to operate and control two booster pump motors on a single system.
These panels are widely used in those applications where maintaining a specific system pressure is required.
Applied Motor Controls’ standard duplex pump panel is designed to provide both “alternating” and “duplexing” modes.
Alternating mode: This function provides for relatively equal wear of the two pump motors, typically of the same HP rating, driven by the controller by reversing the “Lead” and “Lag” roles of the motors on each successive cycle. Automatic alternation is accomplished when one or both motors come to a stop.
​
Duplexing mode: This mode provides stand-by capacity for use of a second pump motor when the system demand exceeds the normal requirements of a single motor, or when one of the motors fails.
Applied Motor Controls offers a wide range of UL-listed factory-installed options that can enhance the control and protection of the pumps.
Standard Features
-
Type 3R enclosure for use outdoors. Rain and sleet resistant. Fully welded steel construction with hinged door and provisions for padlocking​​
​
-
Gray powder-coating finish suitable for use in harsh environments​
​
-
Power Terminal Block for termination of line supply cables
​
-
Choice of two disconnects: Fusible Switches, or Thermal-Magnetic Molded Case Circuit Breakers​
​
-
Fusible Disconnect Switches include factory-installed J-Class time-delay dual-element current-limiting power fuses
​
-
(2) Through the door rotary disconnect operators with provisions for padlocking in the off position​
​​
-
(2) Full Voltage Magnetic Motor Starters with 120VAC coil voltage​
​​
-
(2) Solid State Class 10 Overload Relays with adjustable trip point and inherent protection against loss of phase​
​
-
Solid State Duplex Alternator with Alternating and Duplexing Functions
​
-
120V Control Circuit Transformer with primary and secondary protective fuses
​
-
(2) Hand-Off-Auto Selector Switches
​
-
(2) Terminal Blocks for two remote pressure switches
​
-
Grounding Lug
​
-
UL 508 Listed Industrial Controls​
​​​

-
Fusible Type Panels include J-Class Power Fuses
-
Unless otherwise specified, Starter Coil Voltage is 120VAC
-
Call factory for HP and Voltages not shown​​​​